Presence and proximity sensors

How PIR and radar presence sensors and inductive and capacitive proximity sensors work, where they miss or falsely trigger, and what to check.

Core

Two ways to sense people and two ways to sense objects A passive infrared sensor and a millimetre-wave radar for presence, and inductive and capacitive sensors for proximity, each with what it responds to and how it can mislead you. Passive infrared (PIR) Sees heat moving Two elements in opposition give a signal only as heat crosses Used in occupancy sensors for lighting Watch for a still person gives no signal; head-on approach and typing are hard Needs line of sight; nominal limit about 15 ft (4.6 m) Millimetre-wave radar Sees tiny motion Typing or breathing, so a still person stays detected As one maker describes it Watch for it senses through glass, plastic, wood and drywall, so it can be hidden behind a room's walls Inductive proximity Switches on metal One maker: Sn set with a 1 mm FE 360 steel plate, after IEC 60947-5-2 Watch for other metals, one maker FE 360 steel Sn Stainless steel 0.85 Aluminium 0.4 Brass 0.4 Copper 0.3 Check assured only within 0.81 × Sn Capacitive proximity Also senses non-metals and liquids, even through a non-metallic tank wall Watch for low permittivity, one maker Grounded metal 1 Water 1 Glass 0.6 PVC 0.45 Dry paper 0.25 False triggers build-up, condensation
Two ways to sense people and two to sense objects: what each responds to, how it can mislead you, and how target material shrinks a proximity sensor's range.

Key points

  1. A passive infrared (PIR) sensor has two pyroelectric elements arranged in opposition, so it gives a signal only when heat moves across its field of view. A still person gives none, so lights can go off on someone sitting still. One maker adds that PIR can struggle with a person approaching head-on.123
  2. A US Department of Energy guide (by PNNL) says wireless PIR occupancy sensors are less adept at small movements like typing, need direct line of sight, have a nominal limit of about 15 ft (4.6 m) and should not sit near HVAC supply vents. One maker adds that detection gets hard as surroundings near body temperature.32
  3. Occupancy sensors turn lights off or down in empty rooms. A US federal guide cites an office study that saved 46 % of lighting energy with a 1-minute delay, 32 % with 10 minutes and 22 % with 30 minutes, but says very short delays often go with unhappy occupants and that NEMA guidelines recommend 15 minutes.3
  4. One maker says millimetre-wave radar presence sensors pick up movements as slight as typing or breathing, so a still person stays detected. It also says its radar senses through glass, plastic, wood and drywall, so it can be hidden behind a picture or even behind a room's walls.42
  5. An inductive proximity sensor switches on metal. One maker defines its rated operating distance Sn after IEC 60947-5-2, measured with a 1 mm thick FE 360 steel plate, and gives reduction factors of 0.85 for stainless steel, 0.4 for aluminium or brass and 0.3 for copper. It assures switching only within 0.81 × Sn.5
  6. A capacitive proximity sensor also detects non-metals and liquids, even through a non-metallic tank wall, but less well at low permittivity: one maker's factors are 1 for grounded metal and water, 0.6 for glass, 0.45 for PVC, 0.25 for dry paper. Another lists false triggering from build-up or condensation.67
  7. India's Energy Conservation and Sustainable Building Code 2024 (BEE) needs automatic shutoff on at least 90 % of interior lighting by wattage in the commercial buildings it covers. Occupancy sensors qualify if they switch off, or dim by at least 80 %, within 15 minutes of a space emptying; meeting rooms must have them.8as of 19 November 2026

Common mistakes

  • Expecting a PIR sensor to notice someone sitting still. It responds only to heat moving across its view, so lights can switch off on a still occupant.
  • Using an inductive sensor's rated distance Sn for an aluminium or brass target. One maker's factor for both is 0.4, and it assures switching only within 0.81 × Sn even for steel.
  • Assuming a radar presence sensor's view ends at the walls. One maker says its radar senses through glass, wood and drywall, so think about what moves beyond thin partitions.