Presence and proximity sensors
How PIR and radar presence sensors and inductive and capacitive proximity sensors work, where they miss or falsely trigger, and what to check.
Key points
- A passive infrared (PIR) sensor has two pyroelectric elements arranged in opposition, so it gives a signal only when heat moves across its field of view. A still person gives none, so lights can go off on someone sitting still. One maker adds that PIR can struggle with a person approaching head-on.123
- A US Department of Energy guide (by PNNL) says wireless PIR occupancy sensors are less adept at small movements like typing, need direct line of sight, have a nominal limit of about 15 ft (4.6 m) and should not sit near HVAC supply vents. One maker adds that detection gets hard as surroundings near body temperature.32
- Occupancy sensors turn lights off or down in empty rooms. A US federal guide cites an office study that saved 46 % of lighting energy with a 1-minute delay, 32 % with 10 minutes and 22 % with 30 minutes, but says very short delays often go with unhappy occupants and that NEMA guidelines recommend 15 minutes.3
- One maker says millimetre-wave radar presence sensors pick up movements as slight as typing or breathing, so a still person stays detected. It also says its radar senses through glass, plastic, wood and drywall, so it can be hidden behind a picture or even behind a room's walls.42
- An inductive proximity sensor switches on metal. One maker defines its rated operating distance Sn after IEC 60947-5-2, measured with a 1 mm thick FE 360 steel plate, and gives reduction factors of 0.85 for stainless steel, 0.4 for aluminium or brass and 0.3 for copper. It assures switching only within 0.81 × Sn.5
- A capacitive proximity sensor also detects non-metals and liquids, even through a non-metallic tank wall, but less well at low permittivity: one maker's factors are 1 for grounded metal and water, 0.6 for glass, 0.45 for PVC, 0.25 for dry paper. Another lists false triggering from build-up or condensation.67
- India's Energy Conservation and Sustainable Building Code 2024 (BEE) needs automatic shutoff on at least 90 % of interior lighting by wattage in the commercial buildings it covers. Occupancy sensors qualify if they switch off, or dim by at least 80 %, within 15 minutes of a space emptying; meeting rooms must have them.8as of 19 November 2026
Common mistakes
- Expecting a PIR sensor to notice someone sitting still. It responds only to heat moving across its view, so lights can switch off on a still occupant.
- Using an inductive sensor's rated distance Sn for an aluminium or brass target. One maker's factor for both is 0.4, and it assures switching only within 0.81 × Sn even for steel.
- Assuming a radar presence sensor's view ends at the walls. One maker says its radar senses through glass, wood and drywall, so think about what moves beyond thin partitions.
Spotted a mistake, or found this useful?
Tell usSources
- Occupancy Detection Using Passive Infrared-Based Technology (SLLA603, March 2023) · Texas Instruments · Reference
- Passive Infrared (PIR) (Radar Academy, technology comparisons) · Texas Instruments · Vendor page
- Wireless Occupancy Sensors for Lighting Controls: An Applications Guide for Federal Facility Managers (PNNL-SA-115014, December 2019) · U.S. Department of Energy, Federal Energy Management Program (prepared by Pacific Northwest National Laboratory) · Reference
- Low Power mmWave Radar Solution Enables New Functionality in Battery Powered Proximity Sensing Products (SWRA766, January 2023) · Texas Instruments · Reference
- Inductive Sensors | Operating Distance (Operating Distance as Central Characteristic) · Pepperl+Fuchs · Vendor page
- Capacitive Sensors | Operating Distance (Operating Distance as Central Characteristic) · Pepperl+Fuchs · Vendor page
- Medical Liquid-Level Applications with Enhanced Capacitive Sensor Technology (white paper) · Balluff · Vendor page
- Energy Conservation and Sustainable Building Code 2024 (commercial buildings) · Bureau of Energy Efficiency, Ministry of Power, Government of India · Regulation