# Temperature and humidity sensors

How RTDs, thermistors, thermocouples and capacitive RH sensors work, and how heat, sunlight and damp air make their readings wrong.

Page: https://dharanova.com/learn/temperature-and-humidity-sensors · Track: Sense · Level: Core · Facts last checked 18 November 2026

Read first: [What a sensor actually is](https://dharanova.com/learn/what-is-a-sensor.md), [Sensor families](https://dharanova.com/learn/sensor-families.md), [Calibration, drift and traceability](https://dharanova.com/learn/calibration-and-drift.md)

Diagram: Top: sunlight (an unshielded thermometer may be 25 K off in extreme cases) and heat from processors and displays warm the sensor above the air, so temperature reads high and RH low; at 90 %RH, 1 °C of error is 5 %RH. Fix: shield and isolate it. Bottom left: a capacitive RH sensor, a polymer film between two electrodes that absorbs water in proportion to RH. Bottom right: damp air makes it read high, 100 %RH at 95 %RH (WMO), or +3 %RH after 60 h above 80 %RH (one maker); bake to recondition after extreme exposure. Strip: IMD's 2022 tender asked for ±3 %RH, Pt100 ±0.35 °C, 9 louvres.

## Key points

1. A Pt100 platinum RTD has a resistance of 100 Ω at 0 °C that rises almost linearly with temperature; its resistance-temperature relationship is standardised in IEC 60751. [1][2]
2. An NTC thermistor's resistance falls as temperature rises, steeply and non-linearly, so readings must be linearised in software, for example with the Steinhart-Hart equation, a polynomial fit or a lookup table. [3]
3. A thermocouple generates a voltage from the temperature difference between its junctions (the Seebeck effect), so it needs cold-junction compensation to report an absolute temperature. [4]
4. Relative humidity (RH) is the water vapour pressure in air as a percentage of the saturation vapour pressure at the same temperature. Warm air can hold more water, so RH changes when temperature changes even if the water content does not. The dew point is the temperature at which that air would be saturated. [5][6]
5. A capacitive RH sensor's active part is a polymer film between two electrodes, the top one permeable to water. The film absorbs water in proportion to RH, changing its dielectric properties and capacitance. WMO calls it meteorology's leading technology; electronic RH sensors are common in automatic weather stations. (as of 18 November 2026) [5]
6. One maker's datasheet for a digital RH sensor family gives typical accuracy of ±1.0 to ±1.8 %RH at 25 °C mid-range, wider near 0 and 100 %RH; hysteresis 0.8 %RH; drift typically under 0.2 %RH a year in normal use; best performance at 5 to 60 °C and 20 to 80 %RH. All are for the bare sensor. [7]
7. High or condensing humidity can make RH sensors drift, usually upwards; WMO's example: 100 %RH read at 95 %RH. One maker gives +3 %RH after 60 h above 80 %RH, recovering by itself in normal conditions. After extreme exposure it suggests 10 h at 100 to 105 °C below 5 %RH, then 12 h at 20 to 30 °C and about 75 %RH. [5][7][8]
8. One maker's design guide says heat from nearby processors, power electronics or displays, mostly through the circuit board, makes temperature read high and RH low; in extreme cases such as 90 %RH, 1 °C of error gives 5 %RH. It advises distance, thin traces, milled slits round the sensor and shielding from heated air. [6]
9. A thermometer exposed in the open absorbs radiation; WMO says usual operational ones may differ from air by 25 K in extremely unfavourable conditions, so shield them. A louvred screen can still read high in strong sun and calm wind, perhaps 2.5 K in extreme cases; a sun-warmed screen can make RH read falsely low. [9][5]
10. In a 2022 tender for satellite weather stations, the India Meteorological Department asked for a capacitive or solid-state RH sensor accurate to ±3 %RH or better including non-linearity, hysteresis and repeatability, and a Pt100 accurate to ±0.35 °C or better in a naturally ventilated shield of at least 9 louvres. (as of 18 November 2026) [10]

## Common mistakes

- Mounting a humidity sensor right next to a processor or display, then trusting the RH it reports. Their heat makes the sensor read temperature high and RH low.
- Leaving a temperature and humidity sensor in the sun without a radiation shield, or in a screen that heats up, and treating it as air temperature.
- Trusting a reading near 100 %RH after a long spell of high or condensing humidity. High humidity can push polymer sensors to read high, for example 100 %RH at 95 %RH.

## Where to go next

- [Environmental sensors for VAHA: wiring, how readings reach the app, and two TVOC data-integrity gaps](https://dharanova.com/whitepapers/vaha-environmental-sensors-tvoc-data-integrity.md): a whitepaper from our lab

## Sources

1. [IEC 60751:2022 Industrial platinum resistance thermometers and platinum temperature sensors](https://webstore.iec.ch/en/publication/63753), IEC
2. [A Basic Guide to RTD Measurements (SBAA275A)](https://www.ti.com/lit/an/sbaa275a/sbaa275a.pdf), Texas Instruments
3. [Methods to Reduce Thermistor Linearization Error, Memory, and Power Requirements Over Wide Operating Temperature Ranges (SNOAA12)](https://www.ti.com/lit/an/snoaa12/snoaa12.pdf), Texas Instruments
4. [A Basic Guide to Thermocouple Measurements (SBAA274A)](https://www.ti.com/lit/an/sbaa274a/sbaa274a.pdf), Texas Instruments
5. [Guide to Instruments and Methods of Observation (WMO-No. 8), Volume I, Chapter 4: Measurement of humidity (preliminary 2018 edition)](https://old.wmo.int/extranet/pages/prog/www/IMOP/publications/CIMO-Guide/Prelim_2018_ed/8_I_4_en_MR_clean.pdf), World Meteorological Organization
6. [Design Guide for Humidity and Temperature Sensors, version 2 (March 2024)](https://sensirion.com/media/documents/FC5BED84/662B494D/Sensirion_Humidity_Temperature_Design_Guide.pdf), Sensirion AG
7. [Datasheet SHT4x: 4th Gen. Relative Humidity and Temperature Sensor, version 7.3 (June 2026)](https://sensirion.com/media/documents/33FD6951/6A7C10A0/HT_DS_Datasheet_SHT4x_V7.3.pdf), Sensirion AG
8. [Handling Instructions for SHTxx Humidity and Temperature Sensors, version 9 (June 2025)](https://sensirion.com/media/documents/6D95AA80/6840311F/HT_Handling_Instructions_SHTxx.pdf), Sensirion AG
9. [Guide to Instruments and Methods of Observation (WMO-No. 8), Volume I, Chapter 2: Measurement of temperature (preliminary 2018 edition)](https://old.wmo.int/extranet/pages/prog/www/IMOP/publications/CIMO-Guide/Prelim_2018_ed/8_I_2_en_MR_clean.pdf), World Meteorological Organization
10. [Section III: Request for Proposal, procurement of datalogger, UHF transmitter, Yagi antenna, sensors and other accessories (satellite AWS), e-tender CRS/SID/PUD-9016(Sat.AWS)/0322/2021-22, 23 March 2022](https://imdpune.gov.in/tenders/Section.III.RFP.pdf), India Meteorological Department, Climate Research and Services, Pune (Ministry of Earth Sciences)