# Presence and proximity sensors

How PIR and radar presence sensors and inductive and capacitive proximity sensors work, where they miss or falsely trigger, and what to check.

Page: https://dharanova.com/learn/presence-and-proximity-sensors · Track: Sense · Level: Core · Facts last checked 19 November 2026

Read first: [What a sensor actually is](https://dharanova.com/learn/what-is-a-sensor.md), [Sensor families](https://dharanova.com/learn/sensor-families.md)

Diagram: PIR, for lighting: signals only as heat crosses its two elements; misses a still person, head-on approach and typing; needs line of sight, nominal limit about 15 ft (4.6 m). Millimetre-wave radar, one maker: sees typing or breathing; senses through glass, plastic, wood and drywall, so can hide behind a wall. Inductive, one maker: Sn after IEC 60947-5-2, set with a 1 mm FE 360 steel plate; stainless 0.85, aluminium, brass 0.4, copper 0.3; assured only within 0.81 × Sn. Capacitive, one maker: grounded metal, water 1, glass 0.6, PVC 0.45, dry paper 0.25; build-up, condensation false-trigger it.

## Key points

1. A passive infrared (PIR) sensor has two pyroelectric elements arranged in opposition, so it gives a signal only when heat moves across its field of view. A still person gives none, so lights can go off on someone sitting still. One maker adds that PIR can struggle with a person approaching head-on. [1][2][3]
2. A US Department of Energy guide (by PNNL) says wireless PIR occupancy sensors are less adept at small movements like typing, need direct line of sight, have a nominal limit of about 15 ft (4.6 m) and should not sit near HVAC supply vents. One maker adds that detection gets hard as surroundings near body temperature. [3][2]
3. Occupancy sensors turn lights off or down in empty rooms. A US federal guide cites an office study that saved 46 % of lighting energy with a 1-minute delay, 32 % with 10 minutes and 22 % with 30 minutes, but says very short delays often go with unhappy occupants and that NEMA guidelines recommend 15 minutes. [3]
4. One maker says millimetre-wave radar presence sensors pick up movements as slight as typing or breathing, so a still person stays detected. It also says its radar senses through glass, plastic, wood and drywall, so it can be hidden behind a picture or even behind a room's walls. [4][2]
5. An inductive proximity sensor switches on metal. One maker defines its rated operating distance Sn after IEC 60947-5-2, measured with a 1 mm thick FE 360 steel plate, and gives reduction factors of 0.85 for stainless steel, 0.4 for aluminium or brass and 0.3 for copper. It assures switching only within 0.81 × Sn. [5]
6. A capacitive proximity sensor also detects non-metals and liquids, even through a non-metallic tank wall, but less well at low permittivity: one maker's factors are 1 for grounded metal and water, 0.6 for glass, 0.45 for PVC, 0.25 for dry paper. Another lists false triggering from build-up or condensation. [6][7]
7. India's Energy Conservation and Sustainable Building Code 2024 (BEE) needs automatic shutoff on at least 90 % of interior lighting by wattage in the commercial buildings it covers. Occupancy sensors qualify if they switch off, or dim by at least 80 %, within 15 minutes of a space emptying; meeting rooms must have them. (as of 19 November 2026) [8]

## Common mistakes

- Expecting a PIR sensor to notice someone sitting still. It responds only to heat moving across its view, so lights can switch off on a still occupant.
- Using an inductive sensor's rated distance Sn for an aluminium or brass target. One maker's factor for both is 0.4, and it assures switching only within 0.81 × Sn even for steel.
- Assuming a radar presence sensor's view ends at the walls. One maker says its radar senses through glass, wood and drywall, so think about what moves beyond thin partitions.

## Sources

1. [Occupancy Detection Using Passive Infrared-Based Technology (SLLA603, March 2023)](https://www.ti.com/lit/pdf/slla603), Texas Instruments
2. [Passive Infrared (PIR) (Radar Academy, technology comparisons)](https://dev.ti.com/tirex/explore/content/radar_academy_3_10_00_1/_build_radar_academy_3_10_00_1/source/tech_comparisons/pir.html), Texas Instruments
3. [Wireless Occupancy Sensors for Lighting Controls: An Applications Guide for Federal Facility Managers (PNNL-SA-115014, December 2019)](https://www.energy.gov/sites/prod/files/2019/12/f70/wireless_occupancy_sensor_guide.pdf), U.S. Department of Energy, Federal Energy Management Program (prepared by Pacific Northwest National Laboratory)
4. [Low Power mmWave Radar Solution Enables New Functionality in Battery Powered Proximity Sensing Products (SWRA766, January 2023)](https://www.ti.com/lit/pdf/swra766), Texas Instruments
5. [Inductive Sensors | Operating Distance (Operating Distance as Central Characteristic)](https://www.pepperl-fuchs.com/en/gp28808), Pepperl+Fuchs
6. [Capacitive Sensors | Operating Distance (Operating Distance as Central Characteristic)](https://www.pepperl-fuchs.com/en/gp30413), Pepperl+Fuchs
7. [Medical Liquid-Level Applications with Enhanced Capacitive Sensor Technology (white paper)](https://www.balluff.com/assets/services/downloads/white-papers/Medical-Liquid-level-applications-with-enhanced-capacitive-sensor-technology.pdf), Balluff
8. [Energy Conservation and Sustainable Building Code 2024 (commercial buildings)](https://beeindia.gov.in/WriteReadData/L45218/7534511430467336.pdf), Bureau of Energy Efficiency, Ministry of Power, Government of India