# Motion and vibration sensors

How machine vibration is sensed with piezoelectric and MEMS accelerometers, how the sensor and its mounting can mislead you, and how to check a reading.

Page: https://dharanova.com/learn/motion-and-vibration-sensors · Track: Sense · Level: Core · Facts last checked 19 November 2026

Read first: [What a sensor actually is](https://dharanova.com/learn/what-is-a-sensor.md), [Analog-to-digital conversion](https://dharanova.com/learn/adc-basics.md), [Sensor families](https://dharanova.com/learn/sensor-families.md)

Diagram: Top: an accelerometer attached four ways. A stud on a smooth, clean surface gives the highest mounted resonance; wax comes close but is limited to 40 °C; a magnetic base adds mass and lowers it; a hand-held probe brings it into the measured range, so suits only checks below 1 000 Hz. Error reaches 10 % at about 0.30 times the mounted resonance. Bottom: the withdrawn ISO 10816-3:2009 judged RMS velocity in mm/s over 10 Hz to 1 000 Hz in zones A (newly commissioned), B (usually fine for continuous use), C (usually unsuitable) and D (may damage the machine).

## Key points

1. MEMS inertial sensors combine an accelerometer (linear acceleration, including gravity) and a gyroscope (angular rate); a magnetometer is often added for heading. Gyroscope readings integrate into orientation that drifts over time without correction. [1]
2. ISO 20816-3:2026, published in October 2026, is the current standard for evaluating vibration of industrial machines running at 120 r/min to 30 000 r/min, measured in situ on shafts, bearings, bearing pedestals or housings close to bearings. It replaces ISO 20816-3:2022, which replaced ISO 10816-3:2009. (as of 19 November 2026) [2][3]
3. ISO 20816-3:2026 assesses vibration measured on shafts, bearings, bearing pedestals or housings close to bearings. On rotating machines, bearing housings are often good accelerometer spots: a short, rigid path, no gaskets. A small shift in position can change readings a lot at high frequencies. [2][4]
4. One maker’s manual says the withdrawn DIN ISO 10816-3:2009 rated machines by RMS velocity in mm/s over 10 Hz to 1 000 Hz (2 Hz to 1 000 Hz below 600 r/min). Zone A was typical of newly commissioned machines, B usually fine for unrestricted continuous use, C usually unsuitable for it, and D may damage the machine. (as of 19 November 2026) [5]
5. In India, BIS lists IS 14817 (Part 3):2017, identical to ISO 10816-3:2009 (industrial machines above 15 kW, 120 r/min to 15 000 r/min, measured in situ), as withdrawn and superseded by IS/ISO 20816-3:2022, which covers machines up to 30 000 r/min. Its committee is MED 28. (as of 19 November 2026) [6][7]
6. A piezoelectric accelerometer has no true DC response: it makes charge only under dynamic forces. A MEMS variable-capacitance one reaches 0 Hz. In one maker's shaker test of three ±50 g sensors per type, MEMS ones were usable (±1 dB) to 3 kHz, piezoelectric ones beyond 10 kHz with about 9 times finer resolution. [4][8]
7. A piezoelectric accelerometer's mounted resonance sets its upper frequency limit. One maker's handbook puts the error at 5 % at about 0.22 times that frequency, 10 % at about 0.30 times and 3 dB at about 0.54 times. Sensors built for very high frequencies are less sensitive; high-sensitivity ones cannot reach them. [4]
8. How the sensor is attached changes that resonance. A stud on a smooth, clean surface gives the highest. Wax comes close but is limited to 40 °C, as it softens. A magnetic base adds mass and lowers it. A hand-held probe pulls it into the measured range, so one maker limits probes to quick spot checks below 1 000 Hz. [4][9]
9. To check a vibration channel in the field, one maker's handbook describes a pocket-sized calibrated exciter giving 10 m/s² RMS at 159.2 Hz (1 000 rad/s), equal to 10 mm/s RMS velocity and 10 µm RMS displacement. Calibration compares a sensor back to back with a reference accelerometer on one vibration source. [4]

## Common mistakes

- Holding an accelerometer on a hand-held probe and trusting readings above 1 000 Hz. The probe pulls the sensor's resonance down into the range you are measuring.
- Expecting a piezoelectric accelerometer to report steady acceleration. It has no true DC response; a MEMS variable-capacitance sensor responds down to 0 Hz.
- Using the ISO 10816-3:2009 zones (since superseded by ISO 20816-3) without matching their quantity and band: RMS velocity in mm/s over 10 Hz to 1 000 Hz.

## Sources

1. [BNO055 Intelligent 9-axis absolute orientation sensor datasheet (BST-BNO055-DS000)](https://www.bosch-sensortec.com/media/boschsensortec/downloads/datasheets/bst-bno055-ds000.pdf), Bosch Sensortec
2. [ISO 20816-3:2026 Mechanical vibration - Measurement and evaluation of machine vibration - Part 3: Industrial machines with operating speeds between 120 r/min and 30 000 r/min](https://committee.iso.org/standard/89922.html), ISO
3. [UNI ISO 20816-3:2023 (ISO 20816-3:2022) preview pages](https://store.uni.com/api/ext/uni-api/version/preview/UNI1612069_EEN), UNI (Ente Italiano di Normazione)
4. [Piezoelectric Accelerometers and Vibration Preamplifiers: Theory and Application Handbook (BB0694, revision November 1987)](https://www.bksv.com/doc/bb0694.pdf), Brüel & Kjær
5. [TF3600 TwinCAT 3 Condition Monitoring: Vibration assessment](https://infosys.beckhoff.com/content/1033/tf3600_tc3_condition_monitoring/2708344331.html), Beckhoff Automation
6. [IS 14817 (Part 3):2017 / ISO 10816-3:2009 Mechanical vibration: Evaluation of machine vibration by measurements on non-rotating parts, Part 3 (Know your standards record)](https://www.services.bis.gov.in/php/BIS_2.0/bisconnect/knowyourstandards/Indian_standards/isdetails/Njc4NA==), Bureau of Indian Standards
7. [IS/ISO 20816 search result (BIS e-Sale): IS/ISO 20816 (Part 3):2022 / ISO 20816-3:2022](https://standardsbis.bsbedge.com/BIS_SearchStandard.aspx?Standard_Number=IS%2FISO+20816&id=0), Bureau of Indian Standards (standards portal operated by BSB Edge)
8. [Vibration Sensor Technology in Predictive Maintenance Applications (white paper)](https://www.te.com/usa-en/whitepapers/sensors/predictive-maintenance-with-vibration-sensors.html), TE Connectivity
9. [Mounting/installing an accelerometer](https://www.kistler.com/AT/en/mounting-installing-an-accelerometer/C00000130), Kistler