# Air quality sensors: gases, VOCs, CO₂ and particles

How low-cost MOX gas, NDIR CO₂ and optical particle sensors work, what their numbers really are, and how each one can mislead you.

Page: https://dharanova.com/learn/air-quality-sensors · Track: Sense · Level: Core · Facts last checked 19 November 2026

Read first: [What a sensor actually is](https://dharanova.com/learn/what-is-a-sensor.md), [Sensor families](https://dharanova.com/learn/sensor-families.md), [Accuracy, precision and resolution](https://dharanova.com/learn/accuracy-precision-resolution.md), [Calibration, drift and traceability](https://dharanova.com/learn/calibration-and-drift.md)

Diagram: MOX gas sensor: heated tin dioxide meets hydrogen, ammonia, ethanol or toluene and its resistance falls; it reports TVOC and eCO₂ as calculated estimates and shifts with temperature, humidity and power-up. NDIR CO₂ sensor: CO₂ in a gas cell absorbs 4.26 µm infrared; it reports ppm; self-calibration takes the lowest level as 400 ppm, but buildings occupied round the clock may sit at 600 to 800 ppm. Particle sensor: particles scatter laser light; it estimates PM2.5 and needs correcting, as one sensor read about 40 % high in an EPA study. Below: reference checks and India's PM limits and methods.

## Key points

1. A metal-oxide (MOX) gas sensor heats a semiconductor, typically tin dioxide, whose resistance falls as reducing gases react with oxygen on its surface. One sensor responds to many gases, such as hydrogen, ammonia, ethanol and toluene. They are used in air cleaners, ventilation control and air quality monitors. [1][2][3]
2. In one maker's data, a MOX sensor's resistance in clean air changes with temperature and humidity, and drops sharply in the first seconds after power-up whatever gas is present, so the maker recommends a start-up delay. Its sensitivity data assume 2 days or more of preheating. [2]
3. Some indoor air quality gas sensors report 'TVOC' and 'eCO₂' (or 'CO₂eq'), calculated by their own algorithms from raw gas signals. eCO₂ is a proxy for CO₂, estimated from VOC levels or from ethanol and hydrogen signals. One returns a fixed 400 ppm CO₂eq and 0 ppb TVOC for 15 s after its initialisation command. [3][4]
4. An NDIR CO₂ sensor measures CO₂ by its infrared absorption at 4.26 µm. In a basic design, light crosses the gas to a detector and less gets through as CO₂ rises. No other commonly encountered gas absorbs there, so NDIR is highly selective. It is used to control ventilation in buildings. [5][6][7][8]
5. Some NDIR CO₂ sensors self-calibrate by taking the lowest level over several days, or a week, as outdoor air at 400 ppm. In buildings occupied round the clock, the lowest may be around 600 to 800 ppm, so the sensor rescales wrongly. Makers offer recalibration against a reference sensor or a known CO₂ level. [6][9][8]
6. Optical particle sensors often need correcting, as aerosol properties and humidity vary. In an EPA study, raw 24-hour PM2.5 mass estimates from one widely used laser-scattering sensor were about 40 % high in most of the US, more at higher humidity; EPA fitted a correction using collocated regulatory monitors. [10]
7. India's National Ambient Air Quality Standards (2009, still in force in 2026) set PM2.5 limits of 40 µg/m³ as an annual mean and 60 µg/m³ over 24 hours, and PM10 limits of 60 and 100 µg/m³. The measurement methods listed for both are gravimetric, 'TOEM' (as printed) and beta attenuation. (as of 19 November 2026) [11][12][13]

## Common mistakes

- Treating eCO₂ or CO₂eq as a measured CO₂ level. It is a proxy estimated from a gas sensor's VOC, or ethanol and hydrogen, signals; an NDIR sensor measures CO₂ by its own absorption.
- Leaving automatic self-calibration on in a building that is occupied round the clock, so the CO₂ sensor slowly learns the wrong baseline.
- Comparing a few minutes of raw PM2.5 sensor readings with a 24-hour limit, with no correction for humidity.

## Where to go next

- [Environmental sensors for VAHA: wiring, how readings reach the app, and two TVOC data-integrity gaps](https://dharanova.com/whitepapers/vaha-environmental-sensors-tvoc-data-integrity.md): a whitepaper from our lab

## Sources

1. [Operating principle: MOS type](https://www.figaro.co.jp/en/technicalinfo/principle/mos-type.html), Figaro Engineering Inc.
2. [Technical Information for TGS2602 (air quality control sensor), revised 09/24](https://www.figaro.co.jp/en/product/docs/tgs2602_technical%20information(en)_rev07.pdf), Figaro Engineering Inc.
3. [Datasheet SGP30: Indoor Air Quality Sensor for TVOC and CO2eq Measurements, version 1.0 (May 2020)](https://sensirion.com/media/documents/984E0DD5/61644B8B/Sensirion_Gas_Sensors_Datasheet_SGP30.pdf), Sensirion AG
4. [Measure VOCs to maintain high indoor air quality (ENS160 technical article)](https://www.sciosense.com/wp-content/uploads/2023/12/ENS160-Technical-Article.pdf), ScioSense B.V.
5. [Carbon Dioxide Sensing—Biomedical Applications to Human Subjects (Dervieux, Théron and Uhring, Sensors 22(1), 188, 2022)](https://pmc.ncbi.nlm.nih.gov/articles/PMC8749784/), MDPI, via PubMed Central (US National Library of Medicine)
6. [Infrared sensor technology and its impact on HVAC CO2 measurement accuracy (application note)](https://www.vaisala.com/en/application-note/infrared-sensor-technology-and-its-impact-hvac-co2-measurement-accuracy), Vaisala
7. [Operating principle: NDIR type](https://www.figaro.co.jp/en/technicalinfo/principle/ndir-type.html), Figaro Engineering Inc.
8. [SCD4x Datasheet, version 1.7 (April 2025)](https://sensirion.com/media/documents/48C4B7FB/67FE0194/CD_DS_SCD4x_Datasheet_D1.pdf), Sensirion AG
9. [Field calibration for SCD30, version 0.2 (September 2018)](https://sensirion.com/en/media/documents/33C09C07/620638B8/Sensirion_SCD30_Field_Calibration.pdf), Sensirion AG
10. [Development and application of a United States-wide correction for PM2.5 data collected with the PurpleAir sensor (Barkjohn, Gantt and Clements, Atmos. Meas. Tech. 14, 4617-4637, 2021)](https://amt.copernicus.org/articles/14/4617/2021/), Copernicus Publications (authors: US Environmental Protection Agency)
11. [National Ambient Air Quality Standards, notification No. B-29016/20/90/PCI-L (Gazette of India Extraordinary, Part III Sec. 4, No. 217, 18 November 2009)](https://cpcb.nic.in/uploads/National_Ambient_Air_Quality_Standards.pdf), Central Pollution Control Board, Government of India
12. [The Environment (Protection) Rules, 1986 (as amended to date), Schedule VII: National Ambient Air Quality Standards, substituted by G.S.R. 826(E), 16 November 2009](https://dpcc.delhi.gov.in/sites/default/files/DPCC/generic_multiple_files/evnrules.pdf), Delhi Pollution Control Committee, Government of NCT of Delhi
13. [Parliament Question: Impact of National Clean Air Programme on PM2.5 levels (Rajya Sabha unstarred Q545, written reply)](https://www.pib.gov.in/PressReleasePage.aspx?PRID=2288316&reg=48&lang=1), Press Information Bureau, Ministry of Environment, Forest and Climate Change